2 The Smartpack2 Basic Controller 8 User's Guide Smartpack2 Basic Controller 350021.013, Issue 1.0, 2010 Jun Connection Drawing Use this drawing as a connection reference for all cabling. You find the exact location of connection terminals, plugs and DIP switches, to chapter “ Location of by referring Terminals, Ports, LEDs”, page 6. 1 Introduction 2 User's Guide Smartpack2 Master Controller 350020.013, Issue 2.0, 2014 Jan DC Power Supply Systems SAFETY and ENVIRONMENTAL PRECAUTIONS The product warranty becomes invalid if the following safety precautions are not followed during handling, installation, commissioning and general use/operation of Eltek DC power supply system. General Precautions. Manuals and User Guides for Eltek flatpack2. We have 2 Eltek flatpack2 manuals available for free PDF download: User Manual Eltek flatpack2 User Manual (40 pages).
Type: Operation & user’s manual for Eltek Smartpack2
Pages: 32
28 User's GuideSmartpack2 Master Controller350020.013, Issue 2.0, 2014 Jan
(a)Manual Reset
The DC power system can be configured with automatic or manual alarm reset.
When Manual Alarm Reset is enabled -- and the alarm condition no longer
exists -- the operator must reset the alarm manually, via the power systems
user interface (web GUI or controller’s front keys).
When the Manual Alarm Reset is disabled, then the Automatic Alarm Reset is
enabled (default). In this case, when an alarm condition no longer exists, the
Eltek Smartpack 2 User Manual
main controller will automatically reset the alarm, by deactivating the alarm
lamps and relays to indicate that normal operation is established.
(b)Hysteresis and Time Delay
(c)Mains Independent
Check this option if you want that the LVD alarm monitor will reconnect the
LVD contactor when the rectifier system output voltage reaches the Reconnect
Voltage limit, regardless whether Mains is ON or OFF. For example, this is
Uncheck this option (Mains dependent) if you want that the LVD alarm
Eltek Smartpack 2 User Guide
monitor will NOT reconnect the LVD contactor until Mains is ON again.
Used with LVD contactors that disconnect the battery bank (LVBD). Check
this option if you want that the LVD alarm monitor will reconnect the LVBD
contactor when the battery temperature is lower than the temperature limit
(e)Disconnect Voltage
Enter a numeric value for the battery voltage drop-down limit. When -- after a
Mains failure -- the battery voltage gradually drops down to this limit; then the
alarm monitor raises the alarm and trips the LVD contactor.
Enter a numeric value for the battery voltage reconnection limit. When the
Mains supply is ON again, the rectifier system output voltage increases to this
limit; then the alarm monitor will reconnect the LVD contactor.
Enter the Time delay or number of seconds the LVD contactor has to be tripped
or disconnected, before the alarm monitor is allowed to reconnect the LVD
An Alarm Output Group (AOG) is a user defined software assignmentthat consists of
grouping together all the outputs that always are activated at the same time.
The outputs --alarm relay outputs and or latching contactors (LVLD and LVBD) –are
Eltek Rectifier Manual
distributed among the power system’s controllers and control units.